NYKW2 Series

    Intelligent Universal

    Intelligent Efficient Safe Comprehensive

    PRODUCT OVERVIEW

    NYKW2 series intelligent universal circuit breakers are mainly used to distribute electric energy and protect lines and power supply equipment from overload, undervoltage, short circuit, single-phase grounding and other faults. It adopts intelligent control unit with various protection modes to improve the reliability of power supply. It also has open communication interface for four remote control functions to meet the requirements of the control center and automation system.

    NYKW2 series intelligent universal circuit breaker complies with GB14048.2 "Low-voltage Switchgear and Controgear—Circuit-breakers" and IEC60947-2 "Low-voltage Switchgear and Controlgear—Circuit-breakers" and other standards.

    ZERO ARC

    Adopts magnetic blowing arc extinguishing technology and multi-layer metal grating structure for arc extinguishing, and gratings are staggeredly arranged in "V" groove, which can effectively improve the arc voltage. Also, the side walls of the arc extinguishing chamber are made of gas-producing materials, which can increase the air pressure in the chamber and facilitate the arc into the arc extinguishing chamber to rapidly extinguish the arc, so that it becomes a zero-arc air circuit breaker.

    HIGH BREAKING CAPACITY

    Adopts dual structure of main and arc contacts, and the rated current is borne by the main contact, and the arc is borne by the arc contact, thus the burning damage caused by the arc to the main contact is very small.

    Designed with new contact support, the electrodynamic repulsion force compensates for contact pressure, so that it has better dynamic and thermal stability. The gas-producing material wraps the movable and static contacts, and the high-pressure gas drives the arc to flow to the arc extinguishing chamber quickly, extending the service life of the contacts.
    The main contact is comb-shaped and composed of a number of contacts in parallel to reduce the electrodynamic repulsion force and improve the heat dissipation effect, which is conducive to the improvement of product performance indicators (reliability, temperature rise, breaking capacity, etc.).

    INTELLIGENCE

    Relying on various sensor technologies, microelectronic technologies and various information transmission technologies, NYKW2 series intelligent circuit breakers integrate the functions of control, measurement and communication, which can better break and protect the circuit. It has a variety of protection functions suitable for different application scenarios in order to meet the requirements of control centers and automation systems, and realize the intelligent operation of circuit breakers.

    ABUNDANT EXPANSION SPACE

    Programmable relay signaling units, zone selective interlocking (ZSI), load monitoring, demand value measurement and other expansion units are available to meet the needs of different applications.

    Technical Parameters

    BASIC TECHNICAL PARAMETERS

    Model Rated operating voltage Ue(V) Rated insulation voltage Ui(V) 50Hz Rated impulse withstand voltage Uimp(V) Casing current Inm(A) Rated currentIn(A) Number of poles Short-circuit breaking capacity Rated short-circuit making capacity Icm(kA) (peak) Rated short-time withstand current Icw(kA)/1s N-phase rated current In(A)
    Rated ultimate short-circuit breaking capacity Icu(kA) Rated operating short-circuit breaking capacity Ics(kA)
    AC400V AC690V AC400V AC690V AC
    400V
    AC
    690V
    AC
    400V
    AC
    690V
    NYKW2-2000 AC400、690 AC1000 AC12000 2000 630 3、4 85 50 65 40 187 105 65 40 100%In
    800 85 50 65 40 187 105 65 40
    1000 85 50 65 40 187 105 65 40
    1250 85 50 65 40 187 105 65 40
    1600 85 50 65 40 187 105 65 40
    2000 85 50 65 40 187 105 65 40
    NYKW2-3200 3200 2000 100 65 65 50 220 143 65 50
    2500 100 65 65 50 220 143 65 50
    2900 100 65 65 50 220 143 65 50
    3200 100 65 65 50 220 143 65 50
    NYKW2-4000 4000 3600 120 85 100 80 264 187 100 80 50%In
    3600 120 85 100 80 264 187 100 80
    NYKW2-6300 6300 4000 120 80 100 65 264 165 100 65
    5000 120 80 100 65 264 165 100 65
    6300 120 80 100 65 264 165 100 65

    NYKW2 Series Controller Catalog

    Controller Model NT-2L NT-M NT-2M NT-3M NT-2H NT-3H
    Display mode Electronic display Digital display Digital display LCD display Digital display LCD display
    Overload long delay protection
    Short-circuit short delay protection
    Short-circuit instantaneous protection
    Grounding fault protection
    Current imbalance protection - -
    Functional test
    Fault memory
    Signal contact output
    Thermal memory
    Self-diagnostics
    MCU operating indication - - - - -
    Current columnar display - - - - -
    Current measurement -
    MCR and override tripping
    Load monitoring -
    Fault status indication and value display
    Voltage measurement -
    Power factor - -
    Power measurement - -
    Electrical energy measurement - -
    Communication function - - - -
    Contact wear indication function - -
    Zone selective interlocking - - - -
    Harmonic measurement - - - -
    Voltage protection - - - -
    Memory of grid history parameters - -
    Counting function - -

    Description: ●   Standard function    〇  Optional function     -  Not supported

    Selection table

    NYKW2 2000 3P 630A Model M Drawer type horizontal wiring Additional functions
    Product code Casing grade Pole No. Rated current Intelligent controller Installation method Additional functions
    NYKW2:
    Intelligent universal circuit
    breaker
    2000A
    3200A
    4000A
    6300A
    3P:3 pole
    4P:4 pole
    630A
    800A
    1000A
    1250A
    1600A
    2000A
    2500A
    2900A
    3200A
    3600A
    4000A
    5000A
    6300A
    2L type
    M type
    2M type
    3M type
    2H type
    3H type
    Fixed horizontal wiring
    Drawer type horizontal wiring
    Fixed vertical wiring
    Drawer type vertical wiring
    Under-voltage tripper
    No-voltage tripper
    External current transformer (3P+N)
    One lock and one key
    Two locks and one key
    Three locks and two keys
    Steel cable type mechanical interlocking
    Technical Parameters

    Basic technical parameters

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :2000

      Rated currentIn(A):630

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

      Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :2000

      Rated currentIn(A):800

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

      Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :2000

      Rated currentIn(A):1000

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

      Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :2000

      Rated currentIn(A):1250

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

      Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :2000

      Rated currentIn(A):1600

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

      Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :2000

      Rated currentIn(A):2000

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

      Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :3200

      Rated currentIn(A):2000

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :100(AC400V);65(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);50(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :220(AC400V);143(AC690V)

      Rated short-time withstand current Icw(kA)/1s :65(AC400V);50(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :3200

      Rated currentIn(A):2500

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :100(AC400V);65(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);50(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :220(AC400V);143(AC690V)

      Rated short-time withstand current Icw(kA)/1s :65(AC400V);50(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :3200

      Rated currentIn(A):2900

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :100(AC400V);65(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);50(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :220(AC400V);143(AC690V)

      Rated short-time withstand current Icw(kA)/1s :65(AC400V);50(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :3200

      Rated currentIn(A):3200

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :100(AC400V);65(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);50(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :220(AC400V);143(AC690V)

      Rated short-time withstand current Icw(kA)/1s :65(AC400V);50(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :4000

      Rated currentIn(A):3600

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :120(AC400V);85(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :100(AC400V);80(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :264(AC400V);187(AC690V)

      Rated short-time withstand current Icw(kA)/1s :100(AC400V);80(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :4000

      Rated currentIn(A):4000

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :120(AC400V);85(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :100(AC400V);80(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :264(AC400V);187(AC690V)

      Rated short-time withstand current Icw(kA)/1s :100(AC400V);80(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :6300

      Rated currentIn(A):4000

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :120(AC400V);80(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :100(AC400V);65(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :264(AC400V);165(AC690V)

      Rated short-time withstand current Icw(kA)/1s :100(AC400V);65(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :6300

      Rated currentIn(A):5000

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :120(AC400V);80(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :100(AC400V);65(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :264(AC400V);165(AC690V)

      Rated short-time withstand current Icw(kA)/1s :100(AC400V);65(AC690V)

      N-phase rated current In(A):100%In

    • Rated operating voltage Ue(V) :AC400、690

      Rated insulation voltage Ui(V) 50Hz:AC1000

      Rated impulse withstand voltage Uimp(V):AC12000

      Casing current Inm(A) :6300

      Rated currentIn(A):6300

      Number of poles :3、4

      Rated ultimate short-circuit breaking capacity Icu(kA) :120(AC400V);80(AC690V)

      Rated operating short-circuit breaking capacity Ics(kA) :100(AC400V);65(AC690V)

      Rated short-circuit making capacity Icm(kA) (peak) :264(AC400V);165(AC690V)

      Rated short-time withstand current Icw(kA)/1s :100(AC400V);65(AC690V)

      N-phase rated current In(A):100%In

    NYKW2 Series Controller Catalog

    • Display mode:Electronic display

      Overload long delay protection:●

      Short-circuit short delay protection:〇

      Short-circuit instantaneous protection:●

      Grounding fault protection:〇

      Current imbalance protection:-

      Functional test:●

      Fault memory:●

      Signal contact output:〇

      Thermal memory:●

      Self-diagnostics:●

      MCU operating indication:●

      Current columnar display:●

      Current measurement:-

      MCR and override tripping:〇

      Load monitoring:-

      Fault status indication and value display:●

      Voltage measurement:-

      Power factor :-

      Power measurement:-

      Electrical energy measurement:-

      Electrical energy measurement:-

      Communication function:-

      Contact wear indication function:-

      Zone selective interlocking:-

      Harmonic measurement:-

      Voltage protection:-

      Memory of grid history parameters:-

      Counting function:-

    • Display mode:Digital display

      Overload long delay protection:●

      Short-circuit short delay protection:●

      Short-circuit instantaneous protection:●

      Grounding fault protection:●

      Current imbalance protection:-

      Functional test:●

      Fault memory:●

      Signal contact output:〇

      Thermal memory:●

      Self-diagnostics:●

      MCU operating indication:-

      Current columnar display:-

      Current measurement:●

      MCR and override tripping:〇

      Load monitoring:〇

      Fault status indication and value display:●

      Voltage measurement:〇

      Power factor :-

      Power measurement:-

      Electrical energy measurement:-

      Communication function:-

      Contact wear indication function:-

      Zone selective interlocking:-

      Harmonic measurement:-

      Voltage protection:-

      Memory of grid history parameters:-

      Counting function:-

    • Display mode:Digital display

      Overload long delay protection:●

      Short-circuit short delay protection:●

      Short-circuit instantaneous protection:●

      Grounding fault protection:●

      Current imbalance protection:〇

      Functional test:●

      Fault memory:●

      Signal contact output:〇

      Thermal memory:●

      Self-diagnostics:●

      MCU operating indication:-

      Current columnar display:-

      Current measurement:●

      MCR and override tripping:〇

      Load monitoring:〇

      Fault status indication and value display:●

      Voltage measurement:〇

      Power factor :〇

      Power measurement:〇

      Electrical energy measurement:〇

      Communication function:-

      Contact wear indication function:●

      Zone selective interlocking:-

      Harmonic measurement:-

      Voltage protection:-

      Memory of grid history parameters:〇

      Counting function:●

    • Display mode:LCD display

      Overload long delay protection:●

      Short-circuit short delay protection:●

      Short-circuit instantaneous protection:●

      Grounding fault protection:●

      Current imbalance protection:〇

      Functional test:●

      Fault memory:●

      Signal contact output:〇

      Thermal memory:●

      Self-diagnostics:●

      MCU operating indication:-

      Current columnar display:-

      Current measurement:●

      MCR and override tripping:〇

      Load monitoring:〇

      Fault status indication and value display:●

      Voltage measurement:〇

      Power factor :〇

      Power measurement:〇

      Electrical energy measurement:〇

      Communication function:-

      Contact wear indication function:●

      Zone selective interlocking:〇

      Harmonic measurement:〇

      Voltage protection:〇

      Memory of grid history parameters:〇

      Counting function:●

    • Display mode:Digital display

      Overload long delay protection:●

      Short-circuit short delay protection:●

      Short-circuit instantaneous protection:●

      Grounding fault protection:●

      Current imbalance protection:〇

      Functional test:●

      Fault memory:●

      Signal contact output:〇

      Thermal memory:●

      Self-diagnostics:●

      MCU operating indication:-

      Current columnar display:-

      Current measurement:●

      MCR and override tripping:〇

      Load monitoring:〇

      Fault status indication and value display:●

      Voltage measurement:〇

      Power factor :〇

      Power measurement:〇

      Electrical energy measurement:〇

      Communication function:●

      Contact wear indication function:●

      Zone selective interlocking:-

      Harmonic measurement:-

      Voltage protection:-

      Memory of grid history parameters:〇

      Counting function:●

    • Display mode:LCD display

      Overload long delay protection:●

      Short-circuit short delay protection:●

      Short-circuit instantaneous protection:●

      Grounding fault protection:●

      Current imbalance protection:〇

      Functional test:●

      Fault memory:●

      Signal contact output:〇

      Thermal memory:●

      Self-diagnostics:●

      MCU operating indication:-

      Current columnar display:-

      Current measurement:●

      MCR and override tripping:〇

      Load monitoring:〇

      Fault status indication and value display:●

      Voltage measurement:〇

      Power factor :〇

      Power measurement:〇

      Electrical energy measurement:〇

      Communication function:●

      Contact wear indication function:●

      Zone selective interlocking:〇

      Harmonic measurement:〇

      Voltage protection:〇

      Memory of grid history parameters:〇

      Counting function:●

    Description: ●   Standard function    〇  Optional function     -  Not supported

    Selection table


    • Product code :NYKW2: Intelligent universal circuit breaker

      Casing grade:2000A/3200A/4000A/6300A

      Pole No.:3P:3 pole/4P:4 pole

      Rated current:630A/800A/1000A/1250A /1600A/2000A/2500A/2900A/3200A/3600A/4000A/5000A/6300A

      Intelligent controller:2L type/Model M/2Model M/3Model M/2H type /3H type/

      Installation method:Fixed horizontal wiring/Drawer type horizontal wiring/Fixed vertical wiring/Drawer type vertical wiring

      Additional functions:Under-voltage tripper/No-voltage tripper/External current transformer (3P+N)/One lock and one key/Two locks and one key/Three locks and two keys/Steel cable type mechanical interlocking